EPS emergency lighting power supply
Application (EPS emergency lighting power supply) |
This kind of emergency lighting (includes metal halogen lamp and sodium lamp ) is suitable for fire occasions or other emergency situations , it is an emergency power supply unit for centralized power supply. |
lnstallation (EPS emergency lighting power supply) |
Floor type, hanging type and inlay type. |
Standby time (EPS emergency lighting power supply) |
90min, GB type (it can be set according to design requirement) |
Specification (EPS emergency lighting power supply) |
0.5KW-10KW Single-phase input (220V, AC) includes:(Standard type) Hanging type: HBED-0.5KW、1KW、1.5KW、2KW Inlay type: HBED-0.5KW、1KW、1.5KW、2KW Floor type :HBED-1KW、1.5KW、2KW、3KW、4KW、5KW、6KW、7KW、 8KW、 9KW、10KW Three-phase input (380V, AC) includes: (Standard type) Floor type: HBED-0.5KW、1KW、1.5KW、2KW、3KW、4KW、5KW、6KW、 7KW、8KW、 9KW、10KW
|
Characteristics (EPS emergency lighting power supply) |
1.Adopt the latest IGBT inversion technology; 2.Adopt mode of centralized power supply, not need special lightings; 3.When offering emergency power supply, it will output sine wave alternating current with stable voltage and frequency, and without noise or environmental pollution; 4.With functions of fire response, computer monitoring and fire control; 5.Isolating transformer outputs; 6.Liquid crystal displays. |
Advantages (EPS emergency lighting power supply) |
1. Simple design, convenient for operation; 2. Low cost, reduction of investment; 3. Long service life, the service life of main engine can be more than 20 years; 4. Batteries free from maintenance, can be duty-cycle operated for 300~500 times; 5. Simple management, automatic instantaneous switching, can be unattended operation; 6. Stable illumination intensity, reliable working, and simple maintenance. |
Technical parameter of HBED series EPS products (EPS emergency lighting power supply) |
Model |
HBED-0.5 KW |
HBED-1 KW |
HBED-1.5 KW |
HBED-2 KW |
HBED-3 KW |
HBED-4 KW |
HBED-5 KW |
HBED-6 KW |
HBED-7 KW |
HBED-8 KW |
HBED-9 KW |
HBED-10 KW |
Capacity (KW) |
0.5 |
1.0 |
1.5 |
2.0 |
3.0 |
4.0 |
5.0 |
6.0 |
7.0 |
8.0 |
9.0 |
10 |
Input |
Max current (A) |
3 |
7 |
13 |
20 |
25 |
30 |
35 |
16 |
20 |
25 |
28 |
30 |
Voltage (V) |
Three phases380V 25%or single phase220V 25% |
Frequency (Hz) |
50Hz ± 5% |
Output |
Rated current (A) |
2.2 |
4.5 |
6.8 |
9.1 |
13.6 |
18.1 |
22.7 |
27.2 |
32 |
36.4 |
41 |
45 |
Voltage (V) |
Normal conditions: as the same as voltage of commercial power Urgent conditions: 220V 5% |
Frequency (Hz) |
Urgent conditions:50Hz 5% Normal conditions: as the same as commercial power |
Switching time |
Less than 5 seconds( in special case, it may be less than 0.25 second) |
Waveform |
Urgent condition: sine wave; Normal conditions: as the same as commercial power |
Time of emergency power supply |
90 minutes (standard) |
Overload capacity |
When loading 120%, it can work normally |
Noise |
When there is commercial power, it stays actionless without noise, <55dB (at emergency power supply) |
Relative humidity |
0~90% |
Ambient temperature |
-24℃ ~40℃ |
Altitude |
2000m below |
Applicable loads |
Suitable for various loads like lighting |
Weight (kg) |
60 |
130 |
180 |
210 |
360 |
410 |
510 |
620 |
700 |
780 |
850 |
940 |
Output loop |
3 |
3 |
3 |
3 |
3 |
3 |
3 |
3 |
3 |
3 |
3 |
3 | |
When used for emergency lighting ,wiring method of lighting. (EPS emergency lighting power supply) |
Output line |
Description |
Wiring method |
Code |
Color |
L |
Red |
Output at commercial power; output at no commercial power (offered by emergency power supply); |
I |
L1 |
Yellow |
No output at commercial power; output at no commercial power (offered by emergency power supply); |
II |
L2 |
Green |
Output at commercial power; no output at no commercial power (not offered by emergency power supply); |
III |
L3 |
|
Output at commercial power; output by fire response control when commercial power is failure; |
IV |
|
|
Can be turned on or off when there is commercial power, emergency power supply outputs when commercial power is failure (offered by emergency power supply); |
V |
N |
Blue |
|
|
PE |
Double color of yellow and green |
|
| | |

|
|